Modbus RTU and Modbus TCP Protocols - Thermal Management Products
69 Liebert
®
IntelliSlot
®
Modbus/BACnet
System Status 30422 1
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Control Mode 30423 1
0 = Internal (Auto)
1 = External (Manual)
Maintenance Ramp 30424 1 %
Auto Restart Delay 30425 40425 1 sec
System On/Off Control 30426 40426 1 0 = Off / 1 = On
System Event Acknowledge/Reset 40427 1
2 = Reset
4 = Acknowledge
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 19 Liebert XDC
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units