6 Series 3000 Transmitters and Discrete Controllers
Series 3000 functional specifications
Housings
Rack-mount
486,2 mm rack-mount housing meets DIN standard 41494
and IEC 297-3
Front panel is rated IP40
Panel-mount
With bezel mounting kit, fits into same cutout as
Micro Motion peripherals. Series 3000 bezel is larger
than bezel on Micro Motion DRT, FMS-3, DMS, NFC, or
NOC; dimensions provided on page 11
Front panel with bezel is rated NEMA IP65 (NEMA 4X)
Field-mount
Compartment with threaded cover contains electronics
Terminal compartment contains non-intrinsically safe
compartment with input and output terminals; and
intrinsically safe compartment with interface/display,
sensor terminals (Model 3700 only), and optional input
and output terminals
Mounting bracket and interface/display rotate to allow
mounting in four different orientations
Rated IP67 (NEMA 4X)
Interface/display
Display
Models 3300 and 3500
Backlit LCD, 128x128 pixel, bit map
Adjustable contrast
Non-glare, chemical-resistant acrylic lens
Models 3350 and 3700
Backlit LCD, 128x128 pixel, bit map
Adjustable contrast
Non-glare tempered glass lens
Suitable for hazardous area installation
Keypad membrane switch
Large pushbuttons with tactile feedback
Software-defined function keys
Chemical-resistant polyester
Weight
Models 3300 and 3500
Maximum 1,6 kg, excluding prepared cables
Models 3350 and 3700
8,6 kg
Electrical connections
Input and output connections
Rack-mount
Type D connectors per DIN standard 41612 (IEC 603-2)
Available as solder tails (standard) or screw terminals
(optional)
Screw terminals accept 0,25 mm
2
to 1,5 mm
2
wires
Panel-mount
Screw terminals (standard) or I/O cable with remote DIN
rail-mount screw terminals (optional)
Remote terminals attach to any of four rail types. I/O cable
is available in lengths of 0,6;1,5 and 3 meters
Terminals accept 0,25 mm
2
to 1,5 mm
2
wires
Field-mount
Two color-coded wiring compartments
Compartment with intrinsically safe terminals has
two 3/4-inch NPT or M20x1,5 conduit openings
Compartment with non-intrinsically-safe terminals has
three 3/4-inch NPT or M20x1,5 conduit openings
Screw terminals accept 0,34 mm
2
to 1,5 mm
2
wires
Power connection
Rack-mount
Screw terminals are fixed to rack chassis
Ground makes first and breaks last
Terminals accept 0,75 mm
2
to 2,5 mm
2
wires
Panel-mount
Screw terminals accept 0,75 mm
2
to 2,5 mm
2
wires
Field-mount
Screw terminals accept 0,75 mm
2
to 4,0 mm
2
wires
Input signals
Non-intrinsically-safe input signals
One 2-wire frequency/pulse input
Frequency range 0-20000 Hz
Minimum pulse width 25 µ-sec
Power sourcing or sinking
Voltage 0-0,8 VDC low state
3-30 VDC high state
Current nominal 5 mA pull-up
Two discrete, momentary inputs
Pulse width 0,15 µ-sec minimum
Voltage 0-0,8 VDC low state
3-30 VDC high state
dry contacts
Intrinsically safe input signals
One 9-wire Coriolis sensor signal input with ground