Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Chapter 6. Operating Procedures Page 27
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
CHAPTER 6.
OPERATING PROCEDURES
CONVERTER MODULES
Refer to UM1C24481500 (Converter Module User Instructions) for converter module
operation instructions.
USING THE CONVERTER SYSTEM
WITH AN ACU+ CONTROLLER
The following outlines the steps to set-up the converter system to be used with an ACU+
controller. Refer to the ACU+ Controller User Instructions (UM1M820BNA) for ACU+
operation.
Set switch position 4 of S1 to the “ON” position. See Figure 3-1.
Remove (and store) Jumper P2. See Figure 3-1.
Connect terminal 1 (CANL) and 2 (CANH) of TB2 to the CAN bus the ACU+ resides
on. See Figure 4-2.
Note: The converter system must be the last device on the CAN bus to function
properly.
Note: If the converter system is used with control/monitoring via an ACU+ controller and
the converter input is powered through a distribution device in the host system,
the ACU+ controller should not be set up to calculate battery current. If battery
current measurement via the ACU+ is desired, the host system must measure
battery current with a battery shunt.
LOCAL INDICATORS AND TEST POINTS
Refer to the Converter Module User Instructions (UM1C24481500) for descriptions of the
local indicators located on the converter modules.
Refer to this section for descriptions of the local indicators and test points located on the
main shelf’s front door.
Local Indicators
The following local indicators are provided on the front door of the main shelf. Refer to
Figure 6-1.
a) Circuit Breaker or Fuse Open (Red LED): Illuminates red if any distribution
fuse or circuit breaker in the system opens.
b) Input Voltage OK (Green LED): Illuminates green when all converter modules
report input voltage is OK. This indicator is off if any converter module reports a
low input voltage condition.