Replacing a Bullet Nose Circuit Breaker or Fuseholder
Note: Refer to Figure 2-5 as this procedure is performed.
Procedure
1) Open the shelf’s front door.
2) Circuit Breaker: Operate a defective circuit breaker to the OFF position.
Fuseholder: Remove the fuse carrier from the mounted fuseholder body by
pulling it straight out.
3) Gently rock the defective circuit breaker or fuseholder up and down while pulling
firmly outward until the circuit breaker or fuseholder is free from the distribution
row.
4) Circuit Breaker: Ensure that the circuit breaker is in the OFF position, and is of
the correct rating.
5) Orient the distribution device as shown in Figure 2-5. Insert the terminals on the
rear of the distribution device into their corresponding sockets on the distribution
row. Ensure the alarm contact on the back of the distribution device makes
contact with the alarm terminal on the mounting circuit card. Push distribution
device in firmly until fully seated in the distribution row.
6) Circuit Breaker: Operate the replacement circuit breaker to the ON position.
Fuseholder: Push the fuse carrier securely back into the mounted fuseholder
body. Note that a polarizing key on the bottom of the carrier prevents the carrier
from being inserted upside down.
7) Verify there are no alarms active.
8) Close the shelf’s front door.