Emerson 3051S Dokumentacja Strona 42

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 41
32
Reference Manual
00809-0100-4001, Rev JA
Section 2: Installation
November 2012
Installation
Always perform a zero trim on the transmitter/manifold assembly after installation to eliminate
any shift due to mounting effects. See Sensor Trim Overview” on page 10.
Three and five-valve configurations shown:
Drain/
Vent
Valve
Drain/
Vent Valve
Equalize
(closed)
Process
Isolate
(open)
Isolate
(open)
H
L
In normal operation the two block
valves between the process and
instrument ports will be open and the
equalizing valve will be closed.
Drain/
Vent Valve
Equalize
(closed)
Process
Isolate
(closed)
Isolate
(open)
H
L
1. To zero the 3051, close the
block valve to the low
pressure (downstream) side
of the transmitter first.
Drain/
Vent
Valve
Drain/
Vent
Valve
Drain/
Vent Valve
Equalize
(closed)
Process
Isolate
(closed)
Isolate
(open)
H
L
3. After zeroing the transmitter,
close the equalizing valve.
Przeglądanie stron 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 221 222

Komentarze do niniejszej Instrukcji

Brak uwag