hazardous location. When used in combustible dust
environment, cable entry in accordance with IP66 or
higher level should be applied.
4. Obey the warning “Keep tight when the circuit is alive.”
5. End users are not permitted to change any internal
components.
6. During installation, use and maintenance of this product,
observe the following standards:
GB3836.13-1997 “Electrical apparatus for explosive gas
atmospheres Part 13: Repair and overhaul for apparatus
used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas
atmospheres Part 15: Electrical installations in hazardous
area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas
atmospheres Part 16: Inspection and maintenance of
electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of
electric device for explosion atmospheres and fire hazard
electrical equipment installation engineering”.
GB12476.2-2006 “Electrical apparatus for use in the
presence of combustible dust Part 1-2: Electrical apparatus
protected by enclosures and surface temperature
limitation-Selection, installation and maintenance”
GB15577-2007 “Safety regulations for dust explosion
prevention and protection”
I3 China Intrinsic Safety
Certificate: GYJ13.1362X; GYJ101312X [Flowmeters]
Standards: GB3836.1-2010, GB3836.4-2010,
GB3836.20-2010, GB12476.1-2000
Markings: Ex ia IIC Ga T4/T5
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use:
a.If the apparatus is fitted with an optional 90V transient
suppressor, it is not capable of withstanding the 500V
insulation test for 1 minute. This must be taken into
account when installing the apparatus.
b.The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however,
care should be taken to protect it from impact or
abrasion if located in Zone 0.
2. The relation between T code and ambient temperature
range is:
3. Intrinsically Safe parameters:
Note 1: FISCO parameters apply to both Group IIC and IIB.
Note 2: [For Flowmeters] When 644 Temperature
Transmitter is used, it should be used with Ex-certified
associated apparatus to establish explosion protection
system that can be used in explosive gas atmospheres.
Wiring and terminals should comply with the instruction
manual of both 644 Temperature Transmitter and
associated apparatus. The cables between 644
Temperatures Transmitter and associated apparatus
should be shielded cables (the cables must have insulated
shield). The shielded cable has to be grounded reliably in a
non-hazardous area.
4. Transmitters comply with the requirements for FISCO field
devices specified in IEC60079-27:2008. For the connection
of an intrinsically safe circuit in accordance with FISCO
Model, FISCO parameters are listed in the table above.
5. The product should be used with Ex-certified associated
apparatus to establish explosion protection system that
can be used in explosive gas atmospheres. Wiring and
terminals should comply with the instruction manual of
the product and associated apparatus.
6. The cables between this product and associated apparatus
should be shielded cables (the cables must have insulated
shield). The shielded cable has to be grounded reliably in a
non-hazardous area.
7. End users are not permitted to change any intern
components but to settle the problem in conjunction with
the manufacturer to avoid damage to the product.
8. During installation, use and maintenance of this product,
observe the following standards:
GB3836.13-1997 “Electrical apparatus for explosive gas
atmospheres Part 13: Repair and overhaul for apparatus
used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas
atmospheres Part 15: Electrical installations in hazardous
area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas
atmospheres Part 16: Inspection and maintenance of
electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of
electric device for explosion atmospheres and fire hazard
electrical equipment installation engineering”.
GB12476.2-2006 “Electrical apparatus for use in the
presence of combustible dust Part 1-2: Electrical apparatus
protected by enclosures and surface temperature
Model
T
code
Temperature
range
HART T5 -60°C Ta +40°C
HART T4 -60°C Ta +70°C
Fieldbus/PROFIBUS/FISCO T4 -60°C Ta +60°C
Flowmeter with 644 Temp
Housing
T4 -40°C Ta +60°C
Input parameters
HART Fieldbus/PROFIBUS FISCO
Voltage U
i
30 V 30 V 17.5 V
Current I
i
200 mA 300 mA 380 mA
Power P
i
0.9 W 1.3 W 5.32 W
Capacitance C
i
0.012 μF 0 μF <5 nF
Inductance L
i
0 mH 0 mH <10 μH