Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 12 of 149
BACnet Communications
BACnet Protocol Implementation Conformance Statement Rev. 2.1
Vendor Name: Liebert Corporation
Product Name: SiteLink Module
Product Model Number: SiteLink (All)
Point Documentation:
The points in this document are listed by object reference name and each exposed BACnet point has information in
the description field detailing what the point is. Both of these BACnet properties can be read and discovered
remotely in addition to the points present value property. This document is not able to define specific object instance
numbers because they are dynamically assigned when the programming for the module is created and will vary from
situation to situation. A report detailing reference name, description and object instance number can be requested
from the startup engineer at the time of the modules commissioning.
If after startup if changes are made or new programs are added the dynamically built AV/BV points list will shift for
all points.
Product Description:
The SiteLink module provides a BACnet Point-to-Point communication exchange between proprietary Liebert
Environmental, Power, UPS units to other BACnet compliant devices. The connection to the SiteLink module is via
EIA-232, 9600 baud, no parity, 8 data bits, 1 stop bit (9600,N,8,1 default.) The SiteLink modules are available in 12
port and 4 port configurations (i.e. 1 port per/ Liebert Unit, 12 Liebert units per/ SiteLink module maximum.)
BACnet Conformance Class Supported:
Class 1
Class 4
Class 2
Class 5
Class 3
x
Class 6
BACnet Functional Groups Supported:
Clock
Files
HHWS
Reinitialize
PCWS
Virtual Operator Interface
Event Initialization
Virtual Terminal
Event Response
Device Communications
COV Event Initiation
Time Master
COV Event Response