Autochangeover Controller AC8
Hardware Compatibility
Liebert Units:
Autochangeover Controller AC8
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Output #1 Status
40001
BS01_x
0=Off, 1=On, 2=Forced Off, 3=Forced On,
4=Hardware On
Output #2 Status
40002
BS02_x
Output #3 Status
40003
BS03_x
Output #4 Status
40004
BS04_x
Output #5 Status
40005
BS05_x
Output #6 Status
40006
BS06_x
Output #7 Status
40007
BS07_x
Output #8 Status
40008
BS08_x
Device #1 Status
40009
BS09_x
30=Not Used, 31=Operating, 32=Standby,
33=Pending, 34=Forced On, 35=Forced
Off, 36=Hardware On, 37=Alarm,
38=Event
Device #2 Status
40010
BS10_x
Device #3 Status
40011
BS11_x
Device #4 Status
40012
BS12_x
Device #5 Status
40013
BS13_x
Device #6 Status
40014
BS14_x
Device #7 Status
40015
BS15_x
Device #8 Status
40016
BS16_x
Temp. Sensor #1 Reading
40017
BS17_x
Modbus Format Signed Integer
Temp. Sensor #2 Reading
40018
BS18_x
Temp. Sensor #3 Reading
40019
BS19_x
Temp. Sensor #4 Reading
40020
BS20_x
Control Points (Set)
Enable Date & Time Sync
Output #1
Force On, Force Off, Return to Normal
Output #2
Output #3
Output #4
Output #5
Output #6
Output #7
Output #8