Emerson Autochangeover Controllers AC8 Instrukcja Użytkownika Strona 31

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 149
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 30
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 31 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Reheat Lockout
40349
349
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
40349
349
BC01_x
Bit 4 on=HL off Bit 5 on=HL on
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Przeglądanie stron 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 148 149

Komentarze do niniejszej Instrukcji

Brak uwag