2-6
EN
Rosemount Inc
Head Mount Transmitter with Threaded Sensor
Refer to Volume 1 of the Rosemount Sensors Product Data Sheet (document
number 00813-0100-2654) for complete sensor and mounting accessory
information.
To complete the assembly, follow the steps as described below.
1. Attach the thermowell to the pipe or process container wall. Install and
tighten thermowells before applying pressure.
2. Attach necessary extension nipples and adapters. Seal the nipple and adapter
threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for severe
environments or to satisfy code requirements.
4. Set the transmitter failure mode switch (see Figure 2-11 on page 2-11).
5. Pull the sensor wiring leads through the extensions and adapters into the
universal head. Mount the transmitter into the universal head by threading
the transmitter mounting screws into the universal head mounting holes.
6. Mount the assembly into the thermowell. Seal adapter threads with
silicone tape.
7. Install conduit for field wiring to the conduit entry of the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact with leads
and terminals.
8. Pull the field wiring leads through the conduit into the universal head. Attach
the sensor and power leads to the transmitter. Avoid the contact with leads
and terminals.
9. Install and tighten the universal head cover. Enclosure covers must be fully
engaged to meet explosion-proof requirements.
Figure 2-5. Typical Model644H Transmitter Mounting Configuration Using
Threaded Style Sensor and Assembly
644-0000A04A
Standard Extension
Threaded
Thermowell
Universal Head
Threaded Style Sensor