SENSOR CONNECTIONS
RTD or Ohm Inputs
The transmitters will accept a variety of RTD configurations, including 2-wire, 3-
wire, 4-wire, and compensation loop designs. If the transmitter is mounted
remotely from a 3-wire or 4-wire RTD, it will operate within specifications, without
recalibration, for lead wire resistances of up to 10 ohms per lead (equivalent to
1,000 feet of 20 AWG wire). In this case, the leads between the RTD and
transmitter should be shielded. If using only two leads, both RTD leads are in
series with the sensor element, so significant errors can occur if the lead lengths
exceed three feet of 20 AWG wire (approximately 0.05 °C/ft).
Thermocouple or Millivolt Inputs
The thermocouple can be connected directly to the transmitter for process
mounting applications. Use appropriate thermocouple extension wire if mounting
the transmitter remotely from the sensor. Make connections for millivolt inputs
with copper wire. Use shielding for long runs of wire.
Figure 2-12. Sensor Wiring Diagrams
Model 644 Sensor Connections Diagram
* Rosemount Inc. provides 4-wire sensors for all single element RTDs. You can use these RTDs in 3-wire
configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
**Thetransmittersmustbeconfiguredfora3-wireRTDinordertorecognizeanRTDwitha
compensation loop.
12341234 12 34 12
3
41234
644-0000B01A
1
2-wire
RTD
and
3-wire
RTD
and
4-wire
RTD
and
T/C
and mV
RTD
with
Comp.
Loop
*
**