The transmitters will accept inputs from a variety of RTD and thermocouple types.
Refer to Figure 2-11 on page 2-11 when making sensor connections.
Use the following steps to wire the transmitter:
1. Connect the positive lead from the power supply to the transmitter terminal
marked + and the negative lead to the transmitter terminal marked (see
Figure 2-10 and Figure 2-12).
2. Tighten the terminal compression screws to ensure adequate contact. No
additional power wiring is required.
3. After making connections, recheck the polarity and correctness of
connections, then turn the power on.
Figure 2-10. Connecting a Communicator to a Transmitter Loop
Figure 2-11. Transmitter Power, Communication, and Sensor Terminals
Model 644H Model 644R
Note: Signal loop may be grounded at any point or left ungrounded.
Note: A HART-based communicator may be connected at any termination point in the signal loop. The signal
loop must have between 250 and 1100 ohms load for communications.
Model 644H Model 644R
250 R
L
1100
Power Supply
250 R
L
1100
644-0000A02A, 0000A02B
Power Supply
1 2 3 4
Sensor Terminals
Communication
Terminals
Meter Connector
Power Terminals
Failure Mode
Switch
Sensor
Terminals
Power/Configuration
Terminals
644-1105E01A,
1260B02D
Failure Mode
Switch