Reference Manual
00809-0600-4026, Rev BA
December 2011
4-9
Rosemount Process Radar
Recommended Actions
Verify that Mounting Considerations described in Section 2 are fulfilled.
If probe is bent, try to straighten it gently. If not possible, a replacement of
the complete probe assembly may be required.
For chamber / Pipe installations consider adding a centering disk at the
bottom of the probe. For more information, see the Rosemount 5300
Series Reference Manual (Document No. 00809-0100-4530) section
“Mounting a Centering Disc for Pipe Installations”.
For flexible probes in nozzles consider using a long stud. For more
information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Mounting Considerations”.
For more information on Common Problems and Recommended Actions,
see the Rosemount 5300 Series Reference Manual (Document No.
00809-0100-4530) section “Surface Pulse Not Found”.
Step 4. Transmitter
Diagnostics Review
Verify that no Errors or unattended Warnings are present.
Figure 4-10. The Diagnostics
window in RRM
To view Diagnostics in Rosemount Radar Master:
Rosemount Radar Master > Tools > Diagnostics
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Diagnostics”.
Step 5. Monitor Level
while Emptying
During Step 1, the current level/interface reading was verified correct. This
step will verify that the transmitter correctly tracks the surface during the
emptying of the tank.
Begin by activating log functionality for the transmitter level/interface output.
Either the DCS-trend or a stand-alone tool can be used:
Rosemount Radar Master > Tools > Log