Reference Manual
00809-0600-4026, Rev BA
December 2011
Rosemount Process Radar
7-4
Figure 7-1. The verification of
measurement data using a
sight-glass
Step 2. Analog Output
Signal Validation
NOTE
This section refers to 4-20 mA/HART units only.
Ensure that the loop has been set to manual mode in the DCS for the
applicable transmitter.
Use the transmitter’s built-in simulation mode to verify the analog output
settings. Output at least one arbitrary level or interface and verify that the
readings in the DCS match up.
Rosemount Radar Master > Tools > Simulation Mode
Figure 7-2. Simulation Mode -
[LT-01)
Also, or alternatively, activate the transmitter’s loop test function. Output 4, 12,
and 20 mA and verify that the readings in the DCS match up.
Rosemount Radar Master > Output > Analog Out > Loop Test