
6
Thermal Expansion Valves
Emerson Climate Technologies
sible to determine that the cause of the trouble call is
because of improper methods of instrumentation rather
than any malfunction of the TXV.
When troubleshooting in mountain areas (such
as Denver, Colorado or Salt Lake City, Utah) use a
Pressure-Temperature chart that has correct readings
such as Emerson Climate Technologies’ 5,000 ft. pocket
chart. Gauge pressures will read lower than they would
at sea level.
TXV Selection
Proper TXV size is determined by the BTU/HR or
tons load requirement, the pressure drop across the
TXV, and the evaporator temperature. Do not assume
that the pressure drop across the TXV is equal to the
difference between discharge and suction pressures at
the compressor. This assumption could lead to incorrect
sizing of the TXV.
The pressure at the TXV outlet will be higher than the
suction pressure at the compressor because of the fric-
tional losses through the distribution header, evaporator
tubes, suction lines, ttings, and hand valves. On rack
systems, the EPR valve also adds substantial pressure
drop.
The pressure at the TXV inlet will be lower than the
discharge pressure at the compressor because of fric-
tional losses created by the length of liquid line, valves
and ttings, and vertical lift. The only exception is if the
TXV is installed considerably below the receiver and
static head built up is more than enough to offset fric-
tional loses. The liquid line should be properly sized for
its actual length plus equivalent length due to tting and
hand valves. Vertical lift in the liquid line adds pressure
drop and thus static head must be included.
The pressure drop across the TXV will be the differ-
ence between the discharge and suction pressures at
the compressor less the pressure drops in the liquid line,
through the distributor, evaporator, and suction line.
ASHRAE tables should be consulted for determining
pressure drops in liquid and suction line.
Here is the procedure for properly selecting a TXV:
1. Determine pressure drop across TXV: using the
maximum and minimum condensing pressures, subtract
the evaporating pressure from each to get the total high-
to-low side pressure drop. From these values subtract
the other possible pressure losses– piping and heat
exchanger losses; pressure drop thru accessories; verti-
cal lift pressure drop; and the pressure drop across the
refrigerant distributor.
2. Consider the maximum and minimum liquid tempera-
tures of the refrigerant entering the TXV and select the
correction factors for those temperatures from the table
below the capacity ratings. Determine the corrected ca-
pacity requirement by dividing the maximum evaporator
load in tons by the liquid correction factors.
3. Select the TXV size from the proper capacity table for
the evaporator temperature, pressure drop available,
and corrected capacity requirement.
4. Select the proper thermostatic charge based on the
evaporator temperature, refrigerant, and whether a
Maximum Operating Pressure (see MOP section) type
charge is needed.
5. Determine connections and whether an externally
equalized model is required. Always use an externally
equalized TXV when a distributor is used.
A solid column of liquid refrigerant is required for
proper TXV operation. Calculate the pressure drop
in the liquid line to determine if there will be enough
subcooling to prevent ash gas. If the subcooling of the
liquid refrigerant from the condenser is not adequate,
then a heat exchanger, liquid subcooler, or some other
means must be used to get enough subcooling to en-
sure solid liquid entering the TXV at all times.
Emerson Climate Technologies has prepared
extended TXV capacity tables. These tables can be
found in the Emerson catalog. Always select a TXV
based on operating conditions rather than nominal TXV
capacities.
Komentarze do niniejszej Instrukcji