31
System Protectors
Emerson Climate Technologies
Cross-section shows desiccant beads surrounding
accordion-type lter element
Typical system arrangements show suction line lter drier
installed ahead of the compressor.
Internal Design
Internally, suction line lter driers employ the
same types of elements as liquid line units. One
is the core type, in which the lter drier consists of
a rigid, cylindrical, porous core that may perform
both the lter and drier functions, or be used in
combination with a separate accordion-type lter
element.
The core type lter drier is available either in a
hermetically sealed conguration or in take-apart
designs with a replaceable element.
The latest advancement is the bead-type unit,
in which the desiccant is compacted into the shell.
This design offers several advantages over older
types, including lower pressure drop, more desic-
cant surface area, and greater capacity.
Application Tips
Using a liquid line lter drier as a suction line
lter drier is not recommended. A suction line lter
drier should provide for greater capacity than a
liquid line unit, for better compressor protection
and for less pressure drop. Two access valves
are required to measure pressure drop across the
suction line lter drier.
Komentarze do niniejszej Instrukcji