Emerson Fluid Chiller Instrukcja Naprawy Strona 7

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 6
3
Thermal Expansion Valves
Emerson Climate Technologies
Changes in load cause the TXV pin to move:
• Increasing the superheat will cause the TXV to open
• Decreasing the superheat will cause the TXV to close
Factory Settings of TXVs
The factory superheat setting of TXVs is made with
the TXV pin just starting to move away from the seat.
The superheat necessary to get the pin ready to move is
called static superheat.
TXVs are designed so that an increase in superheat
of refrigerant gas leaving the evaporator is needed for
the TXV pin to open to its rated position.
This added superheat is known as gradient. For ex-
ample, if the factory static is 6°F superheat, the operat-
ing superheat at the rated stroke or pin position (full load
rating of TXV) will be 10°F to 14°F superheat (See
g. 2).
Manufacturers usually furnish the adjustable type
TXV with a factory static superheat setting of 6°F to
10°F unless otherwise specied.
When using non-adjustable TXVs, it’s important that
they are ordered with the correct factory superheat
setting. For manufacturers production lines it is recom-
mended that an adjustable TXV be used in a pilot model
lab test to determine the correct factory superheat set-
ting before ordering the non-adjustable type TXV.
If the operating superheat is raised unnecessarily
high, the evaporator capacity decreases, since more of
the evaporator surface is required to produce the super-
heat needed to operate the TXV.
A minimum change of superheat to open the TXV is
important because it provides savings in rst cost of the
evaporator and cost of operation.
The TXV described so far is internally equalized,
where the evaporator pressure at the TXV outlet is
admitted internally and allowed to exert its force beneath
the diaphragm. In the next section the externally equal-
ized TXV will be discussed.
External Equalizer
A TXV with an external equalizer is required when the
pressure drop through the evaporator is substantial:
3°F for residential air conditioning
2°F for commercial air conditioning
1°F for refrigeration low temperature range
This is because the pressure drop will hold the TXV
in a fairly “restricted” position and reduce system capac-
ity. The evaporator should be designed or selected for
the operating conditions and the TXV selected and ap-
plied accordingly.
For example, an evaporator is fed by a TXV with an
internal equalizer, where a sizable pressure drop of 10
psi is present (See g. 3). The pressure at point “C”
is 25 psig or 10 psi lower than at the TXV outlet, point
“A”, however, the pressure of 35 psig at point “A” is the
pressure acting on the lower side of the diaphragm in a
closing direction. With the TXV spring set at a compres-
sion equivalent to 10°F superheat or a pressure of 10.4
psig, the required pressure above the diaphragm to
equalize the forces is (35 + 10.4) or 45.4 psig. This pres-
sure corresponds to a saturation temperature of 50°F.
The refrigerant temperature at point “C” must be 50°F
if the TXV is to be in equilibrium. Since the pressure at
this point is only 25 psig and the corresponding satura-
tion temperature is 28°F, a superheat of (50°F - 29°F) or
21°F is required to open the TXV.
This increase in superheat, from 10°F to 21°F means
that more of the evaporator surface needs to be used
to produce this higher superheated refrigerant gas. The
evaporator surface available for absorption of heat is re-
duced and the evaporator is starved before the required
superheat is reached.
P
1
= 45.4 PSIG
P
2
= 35 PSIG
P
3
= 10.4 PSIG
35 PSIG = 40°F
25 PSIG = 29°F
25 PSIG = 50°F
B
C
TXV with internal
equalizer on evaporator with
10 PSI drop.
Fig. 3
A
Since the pressure drop across the evaporator in-
creases with load, the restricting effect becomes worse
when the demand on the TXV capacity is greatest.
Przeglądanie stron 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 71 72

Komentarze do niniejszej Instrukcji

Brak uwag