Symptom Possible Cause Action Remark
Valve is not moving
Digital input has priority to
analogue signal input
Digital input must be activated
and deactivated along with
compressor start and stop
Wrong setting of dipswitches
Adjust the dip switches cor-
rectly. The power supply must
be off during this action
Supply voltage too low
Supply voltage: 24VAC ± 10%
if external ECP-024 is used.
Supply voltage: 24VAC or
VDC ± 10% if external
ECP-024 is not connected
Wrong wiring between valve
and driver
Correct the wiring
Valve operating in reverse
direction
Wrong wiring between driver
and valve
Correct the wiring
The valve is not at the posi-
tion corresponding to input
signal
Digital input of driver has
been jumpered so there is no
synchronization at all
Driver does not show any life Wrong supply voltage applied Change EXDU00
Temporary high voltage such
as 110V/230V may damage
the driver
EXD-U00 TROUBLESHOOTING – (Driver with Auxillary Controller)
Function
Dip Switch Number
1 2 3 4 5 6 7 8
EX4/EX5/EX6 operation 0 1 1 0 1 0 – –
EX7 operation 1 0 0 1 0 1 – –
EX8 operation 1 1 0 1 1 1 – –
4-20 mA analogue input signal – – – – – – – 0
0-10V analogue input signal – – – – – – – 1
With start mode – – – – – – 1 –
Without start mode – – – – – – 0 –
3
4
5
6
7
8
1
0
1
2
Superheat Appears Normal -- System Performs Poorly
Problem Symptoms Causes Corrective Action
Valve Doesn't Feed Properly
1) Poor System Performance
2) Low or Normal Superheat
3) Low Suction Pressure
Unequal Circuit Loading Make modification to balance load
Flow From One Coil Affecting
Another Coil
Correct piping
Low Load Correct conditions causing low load
Mismatched Coil/Compressor Correct match
Incorrect Distributor Install correct distributor
Evaporator Oil-Logged Increase gas velocity through coil
Troubleshooting Electronic Valves & Controls