Reference Manual
00809-0100-4801, Rev FA
October 2010
Rosemount 3051S Series
7-36
SAFETY
INSTRUMENTED
SYSTEMS (SIS)
CERTIFICATION
The safety-critical output of the 3051S with Advanced HART Diagnostic is
provided through a two-wire, 4 - 20 mA signal representing pressure. The
3051S safety certified pressure transmitter is certified to: Low Demand; Type
B.
SIL 2 for random integrity @ HFT=0
SIL 3 for random integrity @ HFT=1
SIL 3 for systematic integrity
3051S Safety Certified
Identification
All 3051S transmitters must be identified as safety certified before installing
into SIS systems.
NOTE
There are three versions of safety certified 3051S pressure transmitters. For
transmitters with a yellow SIS circuit board installed (Output code B), please
refer to Manual Supplement 00809-0700-4801. For transmitters without the
Advanced HART Diagnostics circuit board installed, please refer to Section 6:
Safety Instrumented Systems.
To identify a safety certified 3051S with Advanced HART Diagnostics:
1. Connect a HART host to the transmitter.
2. Check transmitter Revision numbers to verify that Electronics SW rev is
10 or higher and Sensor SW rev is 5 or higher.
Fast Key Sequence - 1, 3, 5, 3
3. Verify that option code DA2 is included in the transmitter model code.
3051S SIS Installation No special installation is required in addition to the standard installation
practices outlined in this document. Always ensure a proper seal by installing
the electronics housing cover(s).
Environmental limits are available in the 3051S Product Data Sheet
(document number 00813-0100-4801). This document can be found at
http://www2.emersonprocess.com/en-US/brands/rosemount/Documentation-and-Drawings/Prod
uct-Data-Sheets/Pages/index.aspx
The loop should be designed so the terminal voltage does not drop below
12.0 Vdc when the transmitter output is 23.0 mA.
Security switch should be in the “ON” position during normal operation. See
Figure 7-30 on page 7-38.
3051S SIS
Commissioning
Use any HART-compliant master to communicate with and verify
configuration of the 3051S Safety Certified transmitter with Advanced HART
Diagnostics.
Revision Numbers
Field Device 3
Electronics Software 10 or higher
Electronics Hardware 1
Sensor Software 5 or higher