Reference Manual
00809-0100-4801, Rev FA
October 2010
Rosemount 3051S Series
A-10
Temperature Limits Ambient
Storage
Process Temperature Limits
At atmospheric pressures and above:
-40 to 185 °F (-40 to 85 °C)
With LCD display
(1)
: -40 to 175 °F (-40 to 80 °C)
With option code P0: -20 to 185 °F (-29 to 85 °C)
(1) LCD display may not be readable and LCD updates will be slower
at temperatures below -4 °F (-20 °C).
-50 to 185 °F (-46 to 85 °C)
With LCD display: -40 to 185 °F (-40 to 85 °C)
Coplanar Sensor Module (3051S_C)
Silicone Fill Sensor
(1)(2)
(1) Process temperatures above 185 °F (85 °C) require derating the
ambient limits by a 1.5:1 ratio. For example, for process
temperature of 195 °F (91 °C), new ambient temperature limit is
equal to 170 °F (77 °C). This can be determined as follows:
(195 °F - 185 °F) x 1.5 = 15 °F,
185 °F - 15 °F = 170 °F
(2) 212 °F (100 °C) is the upper process temperature limit for DP
Range 0.
with Coplanar Flange -40 to 250 °F (-40 to 121 °C)
(3)
(3) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for
pressures below 0.5 psia.
with Traditional Flange -40 to 300 °F (-40 to 149 °C)
(3)(4)
(4) -20 °F (-29 °C) is the lower process temperature limit with option
code P0.
with Level Flange -40 to 300 °F (-40 to 149 °C)
(3)
with 305 Integral Manifold -40 to 300 °F (-40 to 149 °C)
(3)(4)
Inert Fill Sensor
(1)(5)
(5) 32 °F (0 °C) is the lower process temperature limit for DP Range 0.
-40 to 185 °F (-40 to 85 °C)
(6)(7)
(6) For 3051S_C, 160 ° F (71 °C) limit in vacuum service.
(7) Not available for 3051S_CA.
In-Line Sensor Module (3051S_T)
Silicone Fill Sensor
(1)
-40 to 250 °F (-40 to 121 °C)
(3)
Inert Fill Sensor
(1)
-22 to 250 °F (-30 to 121 °C)
(3)
3051S_L Level Transmitter
Syltherm
®
XLT -102 to 293 °F (-75 to 145 °C)
Silicone 704
(8)
(8) Upper limit of 600 °F (315 °C) is available with 1199 seal
assemblies mounted away from the transmitter with the use of
capillaries and up to 500 °F (260 °C) with direct mount extension.
32 to 401 °F (0 to 205 °C)
Silicone 200 -49 to 401 °F (-45 to 205 °C)
Inert (Halocarbon) -49 to 320 °F (-45 to 160 °C)
Glycerin and Water 5 to 203 °F (-15 to 95 °C)
Neobee M-20
®
5 to 401 °F (-15 to 205 °C)
Propylene Glycol and Water 5 to 203 °F (-15 to 95 °C)