Application Engineering
BULLETIN
The Intelligent Store Discus™ product line has recently been introduced on 2D, 3D, and 4D compressors.
This product integrates a number of important sensing and compressor protection functions including:
Network Communications Interface (NCI) for on/off control of the compressor, capacity modulation, and
communication of compressor status to the Computer Process Controls (CPC) E2 rack controller
Low oil pressure protection
Discharge temperature protection
High discharge pressure protection
Low suction pressure protection
In addition, a prominent 7-segment display on the front of the Intelligent Store Discus compressor
indicates at a glance the operational status of the compressor.
This manual is also available from the Emerson Climate Technologies Publications Department (Form 2006CC-15).
Intelligent Store Discus™ V1.0 Operators Manual
AE8-1337 R1
November 2006
Application Engineering
BULLETIN
Przeglądanie stron 0
1 2 3 4 5 6 ... 70 71

Podsumowanie treści

Strona 1 - BULLETIN

1© 2010 Emerson Climate TechnologiesPrinted in the U.S.A.AEApplication EngineeringBULLETINThe Intelligent Store Discus™ product line has recently bee

Strona 2 - Operator’s Manual

10Grommets are included to minimize the chance ofchaffing where the cable passes through sheet metalopenings.Refer to figure 2.11 for details regardin

Strona 3 - Table of Contents

113. Intelligent Store™ Discus®Commissioning ProcedureImportant Note: The following commissioninginstructions (sections 3.0 through 3.9) pertain toE2

Strona 4

123.0 Network SetupBegin the process by logging on. To do this press theLog In/Out button on the E2. When prompted, enter“USER” in the username fiel

Strona 5 - Discus® Compressor

13Figure 3.4 Controller Setup Screen3. Verify that the number of ISD devices listed on theController Setup Screen matches the number ofdevices connect

Strona 6 - 1.2.3 Failsafe Operation

14This will open the suction group setup screen asshown below in figure 3.6:Figure 3.6 Suction Group Setup ScreenFrom this screen you can edit the nam

Strona 7 - 2. Installation Instructions

15When these steps have been completed, the compressor setup screen should look like figure 3.7below:3.3 Configuring AssociationsThe next step links t

Strona 8 - 2.4 Communications Network

16Figure 3.11 ISD Summary ScreenSelect the compressor that you wish to rename andPress F5 (Setup). The ISD Compressor Setup Screenshould be displayed

Strona 9

17compressor OFF. In the case where the module is setfor failsafe OFF the compressor will not run until communications have been re-established with t

Strona 10

183.10 Intelligent Store™ Discus®Commissioning Procedure for E2Firmware Revisions 2.07 through 2.20Each Intelligent Store™ Discus® Compressor module(r

Strona 11 - Commissioning Procedure

19Begin the process by logging on. To do this press theLog In/Out button on the E2. When prompted, enter“USER” in the username field and “PASS” in the

Strona 12 - 3.1 Node Recovery

Emerson Climate TechnologiesIntelligent Store™ Discus®Operator’s ManualAE8-1337 R1

Strona 13 - AE8-1337 R1

Figure 3.20 CST Network Screen (with modulespresent)Figure 3.21 Sample Rack with Intelligent Store™Discus® Compressors Note: Immediately following th

Strona 14

21Sample Rack with Intelligent Store™ Discus® Compressors Figure 3.24 CST Summary Screen (After Renaming)3.15 Suction Pressure MappingTo serve as a c

Strona 15 - 3.4 Compressor Naming

223.16 Remote ResetIn the event of an oil pressure or discharge tempera-ture lockout a manual reset is required to restart thecompressor. This can be

Strona 16 - 3.7 Failsafe Operation

23Figure 3.29 Suction Group Setup ScreenFrom this screen you can edit the name of the suctiongroup, select the control type, and enter the numberof st

Strona 17 - 3.9 ISD Module Status

24Sample Rack with Intelligent Store™ Discus® Compressors- 25° Suction - 15° Suction4DL3A150L-TSK04I35625R3DRHA100E-TFD04I00300R4DS3A220E-TSK04I35631R

Strona 18

25Sample Rack with Intelligent Store™ Discus®Compressors Figure 3.31 Suction Group Setup Screen (CompOuts)3.19 Welded ContactorThis protection featur

Strona 19 - 3.13 Configuring Applications

26Figure 3.33 Suction Group Setup ScreenThe E2 will default to a (Board / Point) application.Before proofing can be programmed the E2 must bechanged t

Strona 20 - 3.14 Compressor Naming

• Under normal operating conditions thecode will switch between InjectionMode (2) and Normal (1) when notusing demand cooling. 3 Low Suction Pressure

Strona 21 - 3.15 Suction Pressure Mapping

28compressor has been off for several seconds will not activate this code.9 Module Supply Voltage Trip - If the modulesupply voltage drops below 170 v

Strona 22 - 3.18 Suction Group Setup

294.2 Status Code Table4.3 Startup CodesUpon initial startup or immediately following a manualreset the Intelligent Store™ Discus® module will dis-pla

Strona 23

3Table of Contents 1 Overview of Emerson Climate Technologies Intelligent Store™ Discus®51.1 Functionality 51.1.1 Diagnostics 51.1.2 Communications 51

Strona 24

30AE8-1337 R1

Strona 27

33AE8-1337 R1

Strona 28

34AE8-1337 R1

Strona 29

35Figure 4.1 Measuring ResistanceAcross Current Relay (the valueshould be less than 3 Ohms with thecompressor running)AE8-1337 R1

Strona 30

36AE8-1337 R1

Strona 31

37AE8-1337 R1

Strona 32

38AE8-1337 R1

Strona 33

39AE8-1337 R1

Strona 34

44.3 Startup Codes 294.4 Status Code Troubleshooting 294.4.1 Normal - Off 304.4.2 Normal - Running 314.4.3 Demand Cooling Injecting 324.4.4 Low Suctio

Strona 35

40Accessory FuseFigure 4.2 Accessory Fuse LocationAE8-1337 R1

Strona 36

41Figure 4.3 Communications WiringAE8-1337 R1

Strona 37

42Flashing dLoss of Communication Mode(continued)Communication Troubleshooting• DC Voltage 2.3v - 2.6v (all devices must be connected to the communica

Strona 38

43Determine ReasonEinstein™ SystemOverride Set to“On”Correct Reasonand Set Einstein™System Overrideto “Off”AE8-1337 R1

Strona 39

44Figure 4.4 3D Voltage SensorConnectionsFigure 4.5 4D Voltage SensorConnectionsAE8-1337 R1

Strona 40

45Contactor FuseFigure 4.6 Contactor FuseLocationAE8-1337 R1

Strona 41

46AE8-1337 R1

Strona 43

485.1 Demand Cooling Service ProceduresThe demand cooling valve injects liquid refrigerantinto the suction manifold to keep the discharge gastemperatu

Strona 44 - Figure 4.5 4D Voltage Sensor

49Intelligent Store™ Discus® Compressors are lowerthan for standard demand cooling compressors. Thisis to compensate for the probe location used on th

Strona 45 - Location

51. Overview of Emerson ClimateTechnologies Intelligent Store™Discus® Compressor The Intelligent Store™ Discus® product line is now available on 2D, 3

Strona 46

505.1.3 Coil Inspection and Replacement (2D / 3D)Refer to figure 5.1 for the location of the injection coil.The coil may be removed by unplugging the

Strona 47

51Note: There are no unique injection valve service procedures for the 4D Intelligent Store™ com-pressor. Use conventional 4D valve change-out procedu

Strona 48 - Compressors

526. Lower the side box to provide wrench clearance tothe injection valve bolt.7. Install a new valve, using new gaskets and torqueto 25 - 30 ft-lb. N

Strona 49 - Jumper Wire

531. Turn off power to the compressor, crank case heater and module.*2. Isolate the compressor and evacuate per accept-ed industry practice.3. Inside

Strona 50

548. Unscrew the high and low pressure cutout switch-es.9. Lift the demand cooling coil off of the injectionvalve (if present).10. Unplug the oil pump

Strona 51 - Screws A

555.3 Module Replacement for 2D / 3DRefer to section 5.6.1, “Determine the ReplacementModule Part Number”. Note that the failed moduleshould be return

Strona 52

56switch with a Schraeder depressor (defla-tor). Refer to the parts list in Appendix C.• Connect the blue “LPCO” leads to the lowpressure switch. Veri

Strona 53

8. Installation of a new front box will be the reverseof these steps.9. If you are replacing a module that has only onefuse in the side, or perhaps no

Strona 54

587. Procedures to remove the head are the same asfor any other Discus® compressor.8. Installation of the module will follow the removalsteps in rever

Strona 55 - 5.4.1 Compressor Replacement

595.6 Replacement Module Information5.6.1 Determine the Replacement ModulePart NumberWhen ordering a replacement module (front box) theaddress (node n

Strona 56

6tions can be a powerful tool for diagnosing systemproblems.The fault history and the record of run cycles maintained in the Intelligent Store™ Discus

Strona 57

60either a compressor or module is replaced. In this waya record can be maintained and the user will be ableto assess the true history of the compress

Strona 58 - Compressor Replacement

61A-1 Wiring Figure A.1 Wiring Diagram of Module, Harness and Deutsch Plugs in Terminal BoxFigure A.2 Low Voltage Plug on 4D Compressors: Pins 1, 2,

Strona 59

62A.2 FusingView From Side BoxView of Terminal BoxFigure 6.1Figure 6.3In-Line Retrofit Contactor Coil FuseFigure 6.2All service modules have two fuses

Strona 60 - 5.10 Lifting Instructions

63(1/2 amp) for the accessory coils, and one fuse(2 amp) for the contactor coil (refer to figure 6.1).Always use a fast-blow fuse for replacement.When

Strona 61 - Appendix A

64Appendix C Aftermarket PartsService # Description962-0902-00 Emerson Climate Technologies Intelligent Store™ Discus® Side Box. Includes side box and

Strona 62 - A.2 Fusing

65905-0911-00 Electrical Terminal Box Cover. Cover Only. For usage with specific Copeland® Brand 3D Discus®Compressors with Emerson Climate Technologi

Strona 63 - Appendix B

66985-0102-10 Emerson Climate Technologies Intelligent Store™ Discus® Module- Node 10. For usage on specificCopeland® Brand 2D, 3D and 4D Discus® Comp

Strona 64 - Appendix C Aftermarket Parts

67Appendix D3D Intelligent Store™ Discus® Reference DrawingAE8-1337 R1

Strona 65

682D Intelligent Store™ Discus® Reference DrawingAE8-1337 R1

Strona 66

694D Intelligent Store™ Discus® Reference Drawing AE8-1337 R1

Strona 67 - Appendix D

72. Installation InstructionsEmerson Climate Technologies, Inc. requires that allcustomers review the recommended guidelines in thepublished Applicati

Strona 68

70Appendix ETechnical SupportFor technical support or assistance in resolving issues with the Intelligent Store™ Discus® Compressor Moduleor with the

Strona 69

1675 West Campbell RoadSidney, OH 45365(937) 498-3011EmersonClimate.com2006CC-15 R2 (10/06) Emerson®, Emerson. Consider It Solved™, Emerson Climate Te

Strona 70 - Technical Support

82.2.1 Current Relay Connections• 2D and 3D compressors have a current relay inthe terminal box (refer to figure 2.1 above). Thecurrent relay is used

Strona 71

9designed for commercial HVAC and Refrigerationapplications. RS-485 hardware connections are usedat the network terminations and at each node (compres