11
3. Intelligent Store™ Discus
®
Commissioning Procedure
Important Note: The following commissioning
instructions (sections 3.0 through 3.9) pertain to
E2 controllers with version 2.21 or later firmware.
If you have an earlier version of firmware we
recommend that you upgrade to the latest version
available. For commissioning instructions
pertaining to E2 controllers with firmware
revisions of 2.07 through 2.20 refer to sections
3.10 through 3.20 of this document.
To determine the firmware revision level in the E2
follow these steps:
1. From the main menu select 7 (System
Configuration).
2. Press 3 (System Information).
3. Press 4 (Firmware Revision).
The E2 should look like figure 3.0 below:
Figure 3.0 Firmware Revision Screen
Each Intelligent Store™ Discus® Compressor module
is connected to the E2 via the RS-485 communica-
tions network. As with other devices, the module must
first be “commissioned” to establish communications
with the rack controller. During this commissioning
process the E2 will designate a specific subnet and
node address for each module (front control box) that
is connected. It will also upload and store a master
record of the model number, serial number, and
programmable settings from each module. Warning:
E2 programs from a previously commissioned
store should not be transferred to the new E2 to
short-cut the commissioning process.
The commissioning process can be broken down into
the following steps:
1. Network Setup
2. Node Recovery
3. Suction Group Setup
a. Suction Group Associations
b. Compressor Run Proofing
4. ISD Setup
a. Compressor Naming
b. Failsafe Operation
c. Remote Reset
There are two main menus that must be accessed to
perform module commissioning. These are the
Network Setup screen and the ISD Compressor
Setup screen. To access these screens, refer to
figures 3.1 and 3.2 on the following page: