When these steps have been completed, the
compressor setup screen should look like figure 3.7
below:
3.3 Configuring Associations
The next step links the ISD devices to the appropriate
compressor/stage in the suction group. Access the
association screen from the main menu by pressing 7
(System Configuration) followed by 7 (Network Setup)
followed by 7 (ISD Associations). Once this has been
done the screen should look like figure 3.8 below:
Figure 3.8 ISD Associations Screen
Using the F4 lookup button, enter the appropriate
suction group for each ISD device. Then, enter the
appropriate stage number for each ISD device. Note
that each compressor is considered as one stage. If
an unloader is present it is considered one stage.
Refer to the sample rack in figure 3.9 along with the
completed ISD Association Screen shown in figure
3.10.
Figure 3.9 Sample Rack with Intelligent Store™
Discus® Compressors
Figure 3.10 Completed ISD Associations Screen
Note: Immediately following the commissioning
process the module may display a status code 1
despite the fact that the compressor is not running.
Once the suction group setup procedure is completed
and a run command is sent to the module, the display
will correspond to the status of the compressor.
3.4 Compressor Naming
During the commissioning process each module is
assigned a node address based upon the order in
which it is found by the E2. The E2 then assigns the
module a name based on the node address. It is often
convenient to change this name to reflect the suction
group and position in the rack for each module. Begin
this process by making a list of each compressor as
well as the suction group and location in the rack.
To rename the modules, access the ISD Compressor
Setup Screen:
1. Press menu to open the Main Menu.
2. Press 5 (Configured Applications).
3. Press 35 (ISD Compressor).
- 25° Suction - 15° Suction
4DL3A150L-TSK
04I35625R
3DRHA100E-TFD
04I00300R
4DS3A220E-TSK
04I35631R
3DRHA100E-TFD
04I00439R
2DC3-050E-TFD
04I00435R
Subnet: 15
Node: 2
Subnet: 15
Node: 5
Subnet: 15
Node: 4
Subnet: 15
Node: 3
Subnet: 15
Node: 1
RACK1COMP1 RACK1COMP2 RACK1COMP3 RACK2COMP1 RACK2COMP2
Comp1
Address
Compressor
Name
Stages
Comp2
Comp3
(unloader)
Comp4
Comp5
(unloader)
Comp1
Comp2
(unloader)
Comp3
AE8-1337 R1