Installation
2.4.3 Mount the transmitter
Figure 2-4 illustrates a typical 3051S MultiVariable transmitter installation site measuring dry
gas with an orifice plate.
Figure 2-4. Typical 3051S MultiVariable installation site
Mounting brackets
The 3051S MultiVariable transmitter can be mounted to a 2-in. pipe or to a panel using an
optional mounting bracket. The B4 Bracket (SST) option is for use with the Coplanar flange
process connection. “Coplanar Flange Mounting Configurations” on page 2-24 shows bracket
dimensions and mounting configurations for the B4 option. Other bracket options are listed in
Tab le 2 -1.
When installing the transmitter to one of the optional mounting brackets, torque the bolts to
125 in-lb. (0,9 N-m).
3051S MultiV
Process
Connections
RTD Cable
Pt 100 RTD
Sensor
Flow