25
Reference Manual
00809-0100-4803, Rev DA
Section 2: Installation
April 2013
Installation
2.4.6 Conduit electrical connector wiring (option GE or GM)
For 3051S MultiVariable transmitters with conduit electrical connectors GE or GM, refer to the
cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe,
non-incendive hazardous locations, install in accordance with Rosemount drawing 03151-1009
to maintain outdoor rating (NEMA 4X and IP66.) For more information, see Appendix B,
page B-1.
2.4.7 Grounding
Transmitter case
Always ground the transmitter case in accordance with national and local electrical codes. The
most effective transmitter case grounding method is a direct connection to earth ground with
minimal impedance (< 1 ). Methods for grounding the transmitter case include:
Internal ground connection
The Internal Ground Connection screw is inside the terminal side of the electronics housing. The
screw is identified by a ground symbol ( ), and is standard on all 3051S MultiVariable
transmitters.
Figure 2-13. Internal ground connection
External ground connection
The External Ground Connection is on the outside of the SuperModule housing. The connection
is identified by a ground symbol ( ). An external ground assembly is included with the option
codes shown in Table 2-3 on page 2-26 or is available as a spare part (03151-9060-0001).