Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
3.8.5 475 Fast keys
Use 3051SMV Engineering Assistant or any HART-compliant master to communicate with and
verify configuration of the 3051S MultiVariable Transmitter.
Table 1 shows the 475 Field Communicator fast keys for the Fully Compensated Mass and Energy
Flow. Table 2 shows the fast keys for the Direct Process Variable Output.
A check () indicates the basic configuration parameters. At a minimum, these parameters
should be verified as part of the configuration and startup procedure.
Table 3-13. Fast keys for fully compensated mass and energy flow output
Function Fast Key Sequence
Absolute Pressure Reading and Status 1,4,2,1,5
Absolute Pressure Sensor Limits 1,4,1,5,8
Absolute Pressure Units 1,3,3,5
Alarm and Saturation Level Configuration 1,4,2,6,6
Alarm and Saturation Levels 1,4,2,6
Analog Output Trim Options 1,2,5,2
Burst Mode Setup 1,4,3,3,3
Burst Mode Options 1,4,3,3,4
Callendar-van Dusen Sensor Matching 1,2,5,5,4
Configure Fixed Variables 1,2,4
Damping 1,3,7
Diaphragm Seals Information 1,4,4,5
Differential Pressure Low Flow Cutoff 1,4,1,1,6
Differential Pressure Reading and Status 1,4,2,1,4
Differential Pressure Sensor Trim Options 1,2,5,3
Differential Pressure Zero Trim 1,2,5,3,1
Differential Pressure Units 1,3,3,4
Energy Rate Units 1,3,3,2
Energy Reading and Status 1,4,2,1,2
Equipped Sensors 1,4,4,4
Field Device Information 1,4,4,1
Flow Calculation Type 1,4,1,1,2
Flow Rate Units 1,3,3,1
Flow Reading and Status 1,4,2,1,1
Gage Pressure Reading and Status 1,4,2,1,6
Gage Pressure Sensor Limits 1,4,1,5,9
Gage Pressure Units 1,3,3,6
LCD Configuration 1,3,8