Emerson Liebert FPC Instrukcja Użytkownika Strona 23

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 100
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 22
1B
Precision Cooling Products
19
Table 10 Liebert XDF
- Status and Coil
Data Description
Status
Coil
Number of Bits
Notes
Temperature Indication
1
10011
11
1
-
Unit Control
-
25
1
-
Reset Alarm
-
26
1
-
Acknowledge Alarm
-
27
1
-
Cabinet Sensor Alarm Enable
10023
23
1
-
Fan On
10025
-
1
-
Cool On
10026
-
1
-
Compressor 1 High Pressure
10037
-
1
-
Compressor 1 Low Pressure
10038
-
1
-
Cond Pump-High Water
10052
-
1
-
Loss Compressor Power
10054
-
1
-
Emergency Damper Fail
10056
-
1
-
High Internal Temperature
10057
-
1
-
Loss of Power
10061
-
1
-
Remote Shutdown
10062
-
1
-
Unspecified Event(s)
1
10064
-
1
-
Unit Hrs Exceeded
10080
-
1
-
Comp 1 Hrs Exceeded
10081
-
1
-
Network Failure
10091
-
1
-
No Connection W/Unit 1
10092
-
1
-
Unit(s) Disconnected
10093
-
1
-
Unit Code Missing
10094
-
-
-
Unit Code Mismatch
10095
-
-
-
Low Memory 1
10097
-
-
-
Ram / Battery Failure
10098
-
-
-
(Parallel Flash) MEMORY 1 FAIL
10100
-
-
-
(Serial Flash) MEMORY 2 FAIL
10101
-
-
-
Front Door Open
10102
-
-
-
Rear Door Open
10103
-
-
-
Digital Scroll Compressor 1
Sensor Fail
10108 -
- -
Low Int Temperature
10110
-
-
-
High Ext Dewpoint
10111
-
-
-
Cabinet Temp Sensor Fail
10112
-
-
-
Cabinet Humidity Sensor Fail
10113
-
-
-
Ambient Temp Sensor Fail
10114
-
-
-
Comp 1 Short Cycle
10132
-
-
-
Reheat Lockout
10140
-
-
-
Humidifier Lockout
10141
-
-
-
Przeglądanie stron 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 99 100

Komentarze do niniejszej Instrukcji

Brak uwag