Precision Cooling Products
23
Table 12 Liebert XDP
with Liebert iCOM
®
- Status and Coil
Data Description
Status
Coil
Number of Bits
Notes
Pump 1 Loss of Flow
10001
-
1
Active on Alarm
Pump 2 Loss of Flow
10002
-
1
Active on Alarm
Fan Issue
10003
-
1
Active on Alarm
System Condensation Detected
10004
-
1
Active on Alarm
Customer Input 1
10005
-
1
Active on Alarm
Supply Chilled Water Over Temp
10006
-
1
Active on Alarm
Supply Chilled Water Temp
Sensor Issue
10007 - 1 Active on Alarm
Supply Refrigerant Over Temp
10008
-
1
Active on Alarm
Supply Refrigerant Under Temp
10009
-
1
Active on Alarm
Supply Refrigerant Temp Sensor
Issue
10010 - 1 Active on Alarm
Ext Air Sensor A Over
Temperature
10011 - 1 Active on Alarm
Ext Air Sensor A Under
Temperature
10012 - 1 Active on Alarm
Ext Air Sensor A Issue
10013
-
1
Active on Alarm
Ext Air Sensor B Over
Temperature
10014 - 1 Active on Alarm
Ext Air Sensor B Under
Temperature
10015 - 1 Active on Alarm
Ext Air Sensor B Issue
10016
-
1
Active on Alarm
Ext Dew Point Over Temperature
10017
-
1
Active on Alarm
Chilled Water Control Valve
Position
10018 - 1 Active on Alarm
Shutdown - Loss Of Power
10019
-
1
Active on Alarm
Pump Short Cycle
10020
-
1
Active on Alarm
Water Under Floor
10021
-
1
Active on Alarm
Smoke Detected
10022
-
1
Active on Alarm
Service Required
10023
-
1
Active on Alarm