Table 29 Liebert NXL with Liebert iCOM Single Module (SMS) - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
System Output Voltage RMS
B-N
30212
-
1
-
VAC
System Output RMS Current
Phs B
30214
-
1
-
A AC
System Output Pct Power
Phase B
30215
-
1
-
%
System Output Power Factor
Phs B
30216
-
1 0.1
-
System Input RMS C-A
30251
-
1
-
VAC
System Input RMS Current
Phase C
30254
-
1
-
A AC
Bypass Input Voltage RMS C-A
30257
-
1
-
VAC
System Output Voltage RMS
C-A
30261
-
1
-
VAC
System Output Voltage RMS
C-N
30262
-
1
-
VAC
System Output RMS Current
Phs C
30264
-
1
-
A AC
System Output Pct Power
Phase C
30265
-
1
-
%
System Output Power Factor
Phs C
30266
-
1 0.1
-
Battery Discharge Time
30309
-
1
-
Seconds
Battery Amp-Hours Consumed
This Discharge
30310
-
1
-
AH
Input Qualification Status
30312
-
1
-
0=Fail
1=Marginal Low
2=Normal
3=Marginal High
Bypass Sync Phase Difference
30313
-
1
-
deg
Bypass SS Overload Time
Remain
30314
-
1
-
Seconds
Bypass Qualification Status
30315
-
1
-
0=Fail
1=Marginal Low
2=Normal
3=Marginal High
Battery Total Discharge Time
30316
-
1
-
Hours
Battery Discharge Power
30317
-
1
-
W
Battery Last Discharge Date
30318
-
2
-
-
Battery Commission Date
30322
-
2
-
-
DC Bus Voltage
30326
-
1
-
VDC
DC Bus Current
30327
-
1
-
A DC
DC Bus Qualification Status
30328
-
1
-
0=Fail
1=Marginal Low
2=Normal
3=Marginal High