3B
UPS Systems
62
Table 29 Liebert NXL with Liebert iCOM Single Module (SMS) - Input and Holding Registers
System Output Pct Pwr (VA)
Phs A
30329
-
1
-
%
System Output Pct Pwr (VA)
Phs B
30330
-
1
-
%
System Output Pct Pwr (VA)
Phs C
30331
-
1
-
%
Output Qualification Status
30332
-
1
-
0=Fail
1=Marginal Low
2=Normal
Inverter Overload Time
Remaining
30333
-
1
-
Seconds
Inverter Output Qualification
Status
30334
-
1
-
0=Fail
1=Marginal Low
2=Normal
Total System Operating Time
Rectifier Pulse Count
30337
-
1
-
1=12 Pulse
2=18 Pulse
Rectifier Input Passive Filter
30338
-
1
-
0=Not Installed
1=Installed
Rectifier Passive Filter Switch
30339
-
1
-
0=Not Installed
1=Installed
Rectifier Active Filter
30340
-
1
-
0=Not Installed
1=Installed
System Status
30342
-
1
-
2=StartUp
8=Normal with Warning
16=Normal with Alarm
UPS Module Type
30343
-
1
-
1=Module (1 + 1)
2=Module (1 + N)
3=Module (N + 1)
4=System Control Cabinet
Static Switch Type
30344
-
1
-
1=Continuous Duty
System Input Power Source
30345
-
1
-
1=Utility (mains)
Input Isolation Transformer
30348
-
1
-
0=Not Installed
System Output Maximum Amp
Rating
30350
-
1
-
A AC