Power Distribution and Power Conditioning Products
45
Table 23 Liebert STS2
, Liebert STS2/PDU
- Input and Holding Registers - STS2
Controller
STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Total Transfer Count
-
40001
1
-
-
Preferred Source
-
40002
1
-
1=Source 1, 2=Source 2
Active Source
-
40003
1
-
1=Source 1, 2=Source 2
Source 1 Volts A-B
-
40004
1
-
V
Source 1 Volts B-C
-
40005
1
-
V
Source 1 Volts C-A
-
40006
1
-
V
Source 1 Current A
-
40007
1
-
A
Source 1 Current B
-
40008
1
-
A
Source 1 Current C
-
40009
1
-
A
Source 1 Frequency
-
40010
1
10
Hz
Source 2 Volts A-B
-
40011
1
-
V
Source 2 Volts B-C
-
40012
1
-
V
Source 2 Volts C-A
-
40013
1
-
V
Source 2 Current A
-
40014
1
-
A
Source 2 Current B
-
40015
1
-
A
Source 2 Current C
-
40016
1
-
A
Source 2 Frequency
-
40017
1
10
Hz
Output kW
-
40018
1
-
kW
Output kVA
-
40019
1
-
kVA
CB 1 Status
-
40024
1
-
Bit 0
CB 2 Status
-
40024
1
-
Bit 1
CB 3 Status
-
40024
1
-
Bit 2
CB 3A Status
-
40024
1
-
Bit 3
CB 4 Status
-
40024
1
-
Bit 4
CB 5 Status
-
40024
1
-
Bit 5
CB Spare 1 Status
-
40024
1
-
Bit 6
CB Spare 2 Status
-
40024
1
-
Bit 7
CB 7 Status
-
40024
1
-
Bit 8
CB 8 Status
-
40024
1
-
Bit 9
Auto Xfer Enabled
-
40025
1
-
Bit 0
Has Dual Out Breakers
-
40025
1
-
Bit 1
Has PDU Equipped
-
40025
1
-
Bit 2
Has 4 pole Switch
-
40025
1
-
Bit 3
Has Shunt Trip
-
40025
1
-
Bit 4