2B
Power Distribution and Power Conditioning Products
47
Table 23 Liebert STS2
, Liebert STS2/PDU
- Input and Holding Registers - STS2
Controller
STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Output Voltage Sense Fail
-
40289
1
-
Bit 12
S1 Voltage Sense Fail
-
40289
1
-
Bit 13
S2 Voltage Sense Fail
-
40289
1
-
Bit 14
S1 SCR Sense Fail
-
40289
1
-
Bit 15
S2 SCR Sense Fail
-
40290
1
-
Bit 0
S1 Current Sense Fail
-
40290
1
-
Bit 1
S2 Current Sense Fail
-
40290
1
-
Bit 2
S1 Gate Drive Fail
-
40290
1
-
Bit 3
S2 Gate Drive Fail
-
40290
1
-
Bit 4
Internal Comm Fail
-
40290
1
-
Bit 5
External Comm Fail
-
40290
1
-
Bit 6
CB1 Shunt Trip Fail
-
40290
1
-
Bit 7
CB2 Shunt Trip Fail
-
40290
1
-
Bit 8
CB6 Neutral Open
-
40290
1
-
Bit 9 (N/A to 4P)
Contactor Neutral Fail
-
40290
1
-
Bit 10 (N/A to 4P)
Heatsink Overtemp
-
40290
1
-
Bit 11
Equipment Overtemp
-
40290
1
-
Bit 12 (N/A to 4P)
Ambient Overtemp
-
40290
1
-
Bit 13 (N/A to 4P)
S1 Undervolts
-
40290
1
-
Bit 14
S1 Undervolts (RMS)
-
40290
1
-
Bit 15
S1 Overvolts
-
40291
1
-
Bit 0
S1 Over/Under Freq
-
40291
1
-
Bit 1
S1 Fail
-
40291
1
-
Bit 2
S2 Undervolts
-
40291
1
-
Bit 3
S2 Undervolts (RMS)
-
40291
1
-
Bit 4
S2 Overvolts
-
40291
1
-
Bit 5
S2 Over/Under Frequency
-
40291
1
-
Bit 6
S2 Fail
-
40291
1
-
Bit 7
S1 Overcurrent
-
40291
1
-
Bit 8
S2 Overcurrent
-
40291
1
-
Bit 9
S1 I-Peak
-
40291
1
-
Bit 10
S2 I-Peak
-
40291
1
-
Bit 11
Sources Out of Sync
-
40291
1
-
Bit 12
Load On Alternate Source
-
40291
1
-
Bit 13