UPS Systems
92
Table 46 Liebert NPower
- Input and Holding Registers - IMP
Controller
Single Module Series - SMS
Liebert Products
Liebert NPower - SMS
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Status Points (View)
Input Voltage A-B
-
40001
1
-
V
Input Voltage B-C
-
40002
1
-
V
Input Voltage C-A
-
40003
1
-
V
Bypass Voltage A-B
-
40004
1
-
V
Bypass Voltage B-C
-
40005
1
-
V
Bypass Voltage C-A
-
40006
1
-
V
Battery Voltage
-
40007
1
-
V
Battery Current
-
40008
1
10
A
Battery Temperature
-
40009 1
-
deg C
Output Voltage A-B
-
40010
1
-
V
Output Voltage B-C
-
40011
1
-
V
Output Voltage C-A
-
40012
1
-
V
Output Current A
-
40013
1
10
A
Output Current B
-
40014
1
10
A
Output Current C
-
40015
1
10
A
Output kVA A
-
40016
1
-
kVA
Output kVA B
-
40017
1
-
kVA
Output kVA C
-
40018
1
-
kVA
Output kW A
-
40019
1
-
kW
Output kW B
-
40020
1
-
kW
Output kW C
-
40021
1
-
kW
Output Frequency
-
40022
1
10
Hz
Rated kVA Percentage
-
40023
1
-
%
Rated kW Percentage
-
40024
1
-
%
Alarm Points
Communications Loss
-
40289
1
-
Bit 0
Battery Fuse Fail
-
40289
1
-
Bit 1
Battery Low Transfer
-
40289
1
-
Bit 2
DC Over Voltage Transient
-
40289 1
-
Bit 3
Input Phase Rotation Error
-
40289
1
-
Bit 4
Rectifier/Trap Fuse Fail
-
40289 1
-
Bit 5
Any of Rectifier / Trap Fuse
Bypass Frequency Error
-
40289
1
-
Bit 6
Bypass Overload Shutdown
-
40289
1
-
Bit 7