Emerson Liebert FPC Instrukcja Użytkownika Strona 40

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 100
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 39
1B
Precision Cooling Products
36
Table 18 Liebert Atlas Air
, Liebert Atlas PEC
, Liebert LECS 15
- Input and Holding
Registers - C10 2-step
Controller
C10
Liebert Products
Liebert Atlas Air
Liebert Atlas PEC
Liebert LECS 15
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Humidifier Service
-
40290
1
-
Bit 2
Filter Service
-
40290
1
-
Bit 3
Humidity Low Level
-
40290
1
-
Bit 4
Battery Level Low
-
40290
1
-
Bit 5
Loss of Power
-
40290
1
-
Bit 6
Local Alarm 1
-
40290
1
-
Bit 7
Local Alarm 2
-
40290
1
-
Bit 8
Setpoints (View)
Return Air Temperature
-
40016
1
10
deg C (R/W)
Return Air Humidity
-
40017
1
10
deg C (R/W)
Supply Air Temperature
-
40018
1
10
deg C (R/W)
High Temp Alarm
-
40025
1
10
deg C (R/W)
Low Temp Alarm
-
40026
1
10
deg C (R/W)
High Hum Alarm
-
40027
1
10
% (R/W)
Low Hum Alarm
-
40028
1
10
% (R/W)
Restart Delay
-
40029
1
-
Seconds (R/W)
Control Points (Set)
Activation Mode
-
40006
1
-
1=On / 0=Off (R/W)
General Alarm Status - 40022 1 -
1=On / 0=Off;
write 0 to reset alarm
Audible Alarm Status - 40023 1 -
1=On / 0=Off;
write 0 to ack alarm
Return Air Temperature
-
40349
1
10
deg C (R/W)
Return Air Humidity
-
40350
1
10
deg C (R/W)
Supply Air Temperature
-
40351
1
10
deg C (R/W)
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.
Przeglądanie stron 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 99 100

Komentarze do niniejszej Instrukcji

Brak uwag