Emerson Liebert FPC Instrukcja Użytkownika Strona 29

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 100
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 28
1B
Precision Cooling Products
25
Table 13 Liebert XDP with Liebert iCOM - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Supply Chilled Water Over Temp
Threshold
30413 40413 1 - deg C
Supply Chilled Water Over Temp
Threshold
30414 40414 1 - deg F
Dew Point Temperature
30415
-
1
0.1
deg C
Dew Point Temperature
30416
-
1
0.1
deg F
Auto Restart Delay
30417
40417
1
-
Seconds
System Control Mode
30418
-
1
-
0=Internal (Auto)
1=External (Manual)
Maintenance Ramp
30419
-
1
-
%
Calculated Next Maintenance
Month
30420
-
1
- -
Calculated Next Maintenance
Year
30421
-
1
- -
System On/Off Control
30422
40422
1
-
0=Off / 1=On
System Event
Acknowledge/Reset
- 40423 1
-
2=Reset
4=Acknowledge
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.
Przeglądanie stron 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 99 100

Komentarze do niniejszej Instrukcji

Brak uwag