Emerson Liebert FPC Instrukcja Użytkownika Strona 98

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 100
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 97
3B
UPS Systems
94
Table 46 Liebert NPower
- Input and Holding Registers - IMP
Controller
Single Module Series - SMS
Liebert Products
Liebert NPower - SMS
Available Points
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes/Units
Equipment Over Temperature
Warning
-
40291 1
-
Bit 5
Any of Aux / Battery /
Ambient / Heatsink / Inlet
Over Temp Warning
Fan Fail
-
40291 1
-
Bit 6
Any of Power Pole Fan 1
/ 2 / 3, Primary Fan 1 / 2 /
3 and System Fan Fail
SBS Unable
-
40291
1
-
Bit 7
Inverter Off By User
-
40291
1
-
Bit 8
Battery low Warning
-
40291
1
-
Bit 9
Battery Test Fail
-
40291
1
-
Bit 10
User Shutdown
-
40291
1
-
Bit 11
Load On Bypass
-
40291
1
-
Bit 12
Input Contact Alarms
-
40291 1
-
Bit 13
Any of Input Contact 1-8
Alarms
Generic Alarms
-
40291 1
-
Bit 14
Any other alarm
conditions that are not
mapped
Bypass Overload
-
40291 1
-
Bit 15
Any of Bypass A / B / C
Overload
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.
Przeglądanie stron 97
1 2 ... 93 94 95 96 97 98 99 100

Komentarze do niniejszej Instrukcji

Brak uwag