Transmitter Configuration and Use: Series 1000 and 2000 Transmitters 141
Troubleshooting DiagramsDefaultsCompensation
Appendix A
Default Values and Ranges
A.1 Overview
This appendix provides information on the default values for most transmitter parameters. Where
appropriate, valid ranges are also defined.
These default values represent the transmitter configuration after a master reset. Depending on how
the transmitter was ordered, certain values may have been configured at the factory.
The default values listed here apply to all Version 4.x transmitters using a Version 2.x core processor.
A.2 Most frequently used defaults and ranges
The table below contains the default values and ranges for the most frequently used transmitter
settings.
Table A-1 Transmitter default values and ranges
Type Setting Default Range Comments
Flow Flow direction Forward
Flow damping 0.8 sec 0.0 – 51.2 sec User-entered value is
corrected to nearest lower
value in list of preset values.
For gas applications, Micro
Motion recommends a value
of 3.2.
Flow calibration factor 1.00005.13 For T-Series sensors, this
value represents the FCF and
FT factors concatenated. See
Section 6.2.2.
Mass flow units g/s
Mass flow cutoff 0.0 g/s Recommended setting is
0.5–1.0% of the sensor’s
rated maximum flowrate.
Volume flow units L/s
Volume flow cutoff 0/0 L/s 0.0 – x L/s x is obtained by multiplying
the flow calibration factor by
0.2, using units of L/s.
Meter factors Mass factor 1.00000
Density factor 1.00000
Volume factor 1.00000