5.3.2 Loop testing with ProLink II
See Figure 5-3 for the loop test procedure. Not all options are available on all
transmitters.
Note the following:
• The mA reading does not need to be exact. You will correct differences
when you trim the mA output. See Section 5.4.
Figure 5-3 ProLink II – Loop test procedure
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
Test
Fix Milliamp 1
Fix Milliamp 2
ProLink Menu
Fix Freq Out
Read Discrete InFix Discrete Out 1
Fix Discrete Out 2
Enter pulses/second
(Hz) value
Toggle remote input
device
Read output at
receiving device
Read output at
receiving device
Loop test successful
UnFix
Check output wiring
Troubleshoot output
Correct?
Read output at
receiving device
ON or OFF
Verify reading at
transmitter
Enter mA value
Ye s No output
Correct?
Fix FrequencyFix mA Fix Discrete Output
Correct? Correct?
Loop test successful Check input wiring
Troubleshoot remote
device
Ye s No input