Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
1-4
Analog Input Block
The Analog Input (AI) Function Block processes the measurements from the
sensor and makes them available to other function blocks. The output value
from the AI block is in engineering units and contains a status indicating the
quality of the measurement. The AI block is widely used for scaling
functionality.
Input Selector Block
The Input Selector (ISEL) Function Block can be used to select the first good,
Hot Backup, maximum, minimum, or average of as many as eight input
values and place it at the output. The block supports signal status
propagation.
Integrator Block
The Integrator (INT) Function Block integrates one or two variables over time.
The block compares the integrated or accumulated value to pre-trip and trip
limits and generates discrete output signals when the limits are reached.
Arithmetic Block
The Arithmetic (ARTH) Function Block provides the ability to configure a
range extension function for a primary input. It can also be used to compute
nine different arithmetic functions.
Signal Characterizer Block
The Signal Characterizer (SGCR) Function Block characterizes or
approximates any function that defines an input/output relationship. The
function is defined by configuring as many as twenty X,Y coordinates. The
block interpolates an output value for a given input value using the curve
defined by the configured coordinates. Two separate analog input signals can
be processed simultaneously to give two corresponding separate output
values using the same defined curve.
PID Block
The PID Function Block combines all of the necessary logic to perform
proportional/integral/derivative (PID) control. The block supports mode
control, signal scaling and limiting, feed forward control, override tracking,
alarm limit detection, and signal status propagation.
The block supports two forms of the PID equation: Standard and Series. You
can choose the appropriate equation using the MATHFORM parameter. The
Standard ISA PID equation is the default selection.
Integrator Block
The Integrator Block is used as a totalizer. This block will accept up to two
inputs, has six options how to totalize the inputs, and two trip outputs.
Control Selector Block
The Control Selector Function Block selects one of two or three inputs to be
the output. The inputs are normally connected to the outputs of PID or other
function blocks. One of the inputs would be considered Normal and the other
two overrides.