Reference Manual
00809-0200-4801, Rev CA
July 2010
D-1
Rosemount 3051S
Appendix D 3051S FOUNDATION fieldbus
Revision 23 Release
New Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-1
New Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-2
NEW FUNCTION
BLOCKS
Compensated Mass Flow Transducer Block
This block has all the functionality of the 3095 MultiVariable Mass Flow
transmitter with its fully compensated real-time mass flow calculation. It uses
the 3095 Engineering Assistant configuration package that contains a built in
property data base with 110 fluids/gases and over 25 different primary
elements to configure the flow calculation. The block can receives Line
Pressure and Temperature measurements from separate Pressure and
Temperature transmitters on the segment.
It also supports fixed static pressure and/or process temp values, entered by
the operator.
The Mass flow value can be displayed on the LCD and can be totalized in the
Integrator Block.
Analog Output Blocks
Two Analog Output Blocks are used bring in the static pressure and
temperature variables needed to calculate mass flow.
Control Selector
The Control Selector is designed to select one of two or three inputs for
control. The selection can be the highest, middle, or lowest. The inputs are
normally connected to the outputs of PID or other function blocks. The block is
configured to use one of the inputs to control its output. The other two inputs
can be configured to override the selected input if the process conditions so
require.
Output Splitter
The output splitter is designed to split the output of one PID or other control
blocks so it can control two valves or actuators. Although there are many uses
for the block, the example below is controlling the temperature inside a
reactor with exothermic reaction. In order to start the reaction, the reactants
have to be heated. The controller signal is split in a way to have the heating
fluid valve controlling the temperature while the cooling valve remains closed.
When the reaction starts, heat is liberated and the heating valve is closed.
The coolant valve takes over. The block allows different combinations of
actions.
Multiple Analog Input
A MAI block was added to publish statistical data from the Advanced
Diagnostic Block.