Reference Manual
00809-0200-4801, Rev CA
July 2010
6-11
Rosemount 3051S
See Table 3-1 for a complete listing of valid Channels for the AI Block.
The SPM Mean and Standard Deviation are always displayed in the unit
inches of water, regardless of the measurement unit configured in the
transducer block for the primary pressure measurement. Therefore, when
configuring an AI Block to read one of the SPM values, the engineering unit of
the XD_SCALE parameter must be set to “inH2O at 68 ºF”.
The OUT_SCALE parameter should be set to the engineering unit and range
which are desired for the mean and standard deviation output. For example, it
is possible to use the OUT_SCALE parameter to convert mean and standard
deviation to some other pressure unit. See “Analog Input (AI) Function Block”
on page 3-8 for additional details on setting the XD_SCALE, OUT_SCALE,
and L_TYPE parameters of the AI function block.
The Multiple Analog Input (MAI) function block can be used to read the mean
and standard deviation from all four SPM blocks simultaneously. The Channel
of the MAI block must be set to 11. The mapping between output parameters
of the MAI and the SPM values is shown in Table 6-2:
The output values from the MAI block are always in the unit inH
2
O.
SPM Configuration with
EDDL
For host systems that support Electronic Device Description Language
(EDDL), using SPM is made easier with step-by-step configuration guidance
and graphical displays. This section of the manual uses AMS Device Manager
version 10.5 for illustrations, although other EDDL hosts could be used as
well.
The SPM Configuration Wizard can be launched by clicking the button
“Statistical Process Monitor Setup” from the page Configure > Guided Setup
This Wizard will take you step-by-step through the parameters that need to be
set in order to configure SPM. On the first screen (Figure 6-7), select which
SPM block (1, 2, 3, or 4) that you want to configure.
Table 6-1. Valid SPM Channels for the AI Block
Channel
SPM Variable
12 SPM1 mean
13 SPM1 standard deviation
14 SPM2 mean
15 SPM2 standard deviation
16 SPM3 mean
17 SPM3 standard deviation
18 SPM4 mean
19 SPM4 standard deviation
Table 6-2. SPM Output Values for the MAI Block
Parameter SPM Variable
OUT1 SPM1 mean
OUT2 SPM1 standard deviation
OUT3 SPM2 mean
OUT4 SPM2 standard deviation
OUT5 SPM3 mean
OUT6 SPM3 standard deviation
OUT7 SPM4 mean
OUT8 SPM4 standard deviation