Follow through the “Add History Collection” dialog (Figure 6-14), to add the
parameter to the DeltaV Historian with the desired sampling period,
compression, etc. By default the sampling period is 60 seconds, as shown in
a. of Figure 6-14. However, there are many diagnostics applications where
one may want to look at changes in the standard deviation much faster than
this. In that case, you will want to set the sampling period to something
smaller.
When adding a standard deviation for history collection in DeltaV, it is
recommended that you not use the default data compression settings. By
default, the DeltaV Historian will log a new data point only when the process
value deviates by 0.01 or more. There are many diagnostics applications
where it is useful to look at changes in the standard deviation that are smaller
than this. Therefore, it is recommended that when logging the standard
deviation, either the Data Compression should be disabled (by unchecking
the appropriate box in b. of Figure 6-14 on page 6-16) or the Deviation (EU)
should be set to a much lower value, for example, 0.001 or 0.0001.
Figure 6-14. DeltaV Add History
Collection: a.) General
Configuration b.) Advanced
Configuration
Refer to the DeltaV Books Online for more details on the DeltaV Continuous
Historian.
After the SPM value has been saved to the historian, when the DeltaV
Process History View is opened for the selected parameter, the graph will be
populated with the historical data currently in the database (Figure 6-15).