Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
C-2
HAZARDOUS
LOCATIONS
CERTIFICATIONS
North American Certifications
FM Approvals
E5 Explosion-proof for Class I, Division 1, Groups B, C, and D, T5 (T
a
= 85 °C); Dust Ignition-proof
for Class II and Class III, Division 1, Groups E, F, and G, T5 (T
a
= 85 °C); hazardous locations;
enclosure Type 4X, conduit seal not required when installed according to Rosemount drawing
03151-1003.
I5/IE Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D, T4 (T
a
= 70 °C for output
options A or X; T
a
= 60 °C for output option F); Class II, Division 1, Groups E, F, and G; Class III,
Division 1; Class I, Zone 0 AEx ia IIC T4 (T
a
= 70 °C for output options A or X; T
a
= 60 °C for
output option F) when connected in accordance with Rosemount drawing 03151-1006;
Non-Incendive for Class I, Division 2, Groups A, B, C, and D; T4 (T
a
= 70 °C for output options A
or X;
T
a
= 60 °C for output option F) Enclosure Type 4X
For entity parameters see control drawing 03151-1006.
Canadian Standards Association (CSA)
All CSA hazardous approved transmitters are certified per ANSI/ISA 12.27.01-2003.
E6 Explosion-proof for Class I, Division 1, Groups B, C, and D; Dust Ignition-proof for Class II and
Class III, Division 1, Groups E, F, and G; suitable for Class I, Division 2, Groups A, B, C, and D,
when installed per Rosemount drawing 03151-1013, CSA Enclosure Type 4X; conduit seal not
required; Dual Seal.
I6/IF Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance
with Rosemount drawings 03151-1016; Dual Seal.
For entity parameters see control drawing 03151-1016.
European Certifications
I1/IA ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X II 1G
Ex ia IIC T4 (T
a
= -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HART Diagnostics
Ex ia IIC T4 (T
a
= -60 °C to 70 °C) -FOUNDATION fieldbus
Ex ia IIC T4 (T
a
= -60 °C to 40 °C) -FISCO
1180
Input Parameters
Loop /
Power
Groups
U
i
= 30 V HART / FOUNDATION fieldbus/ Remote Display /
Quick Connect / HART Diagnostics
U
i
= 17.5 V FISCO
I
i
= 300 mA HART / FOUNDATION fieldbus/ Remote Display /
Quick Connect / HART Diagnostics
I
i
= 380 mA FISCO
P
i
= 1.0 W HART / Remote Display / Quick Connect /
HART Diagnostics
P
i
= 1.3 W FOUNDATION fieldbus
P
i
= 5.32 W FISCO
C
i
= 30 nF SuperModule Platform
C
i
= 11.4 nF HART / HART Diagnostics / Quick Connect
C
i
= 0 FOUNDATION fieldbus / Remote Display / FISCO
L
i
= 0 HART / FOUNDATION fieldbus/ FISCO / Quick
Connect / HART Diagnostics
L
i
= 60 µH Remote Display
RTD Assembly (3051SFx Option T or R)
U
i
= 5 Vdc
I
i
= 500 mA
P
i
= 0.63W