Reference Manual
00809-0200-4801, Rev CA
July 2010
5-9
Rosemount 3051S
ADVANCED
DIAGNOSTICS
TRANSDUCER BLOCK
(ADB)
This section describes error conditions found in the Advanced Diagnostics
Transducer Block. Read Table 5-11 to determine the appropriate corrective
action. Refer to Section 6 for complete information on Advanced Diagnostics.
Table 5-11. Advanced
Diagnostic Block BLOCK_ERR
messages
Condition Name and Description
Other
Out of Service: The actual mode is out of service.
Symptom Possible Causes Recommended Action
PIL or SPM will not go to Learning. ADB Block is not licensed. The
algorithm Status will indicate “Not
Licensed.”
1. Check DIAG_OPTIONS in the Resource Block. PIL/SPM or a
hex value of 0x00000300 should be shown. See "Advanced
Diagnostics Transducer Block" on page 1-3.
Resource Block Actual Mode is
OOS.
Determine why the Resource block is in OOS. Correct problem
then put Resource Block into Auto mode
ADB block Actual mode is OOS. Put ADB block into Auto mode.
The algorithms were not activated
or configured properly..
To activate and configure SPM see page 6-6. To activate and
configure PIL, see page 6-25
For the SPM algorithm only: The
variable to be monitored is in an
unscheduled function block
Download a schedule into the function block. Consult your host
documentation for downloading schedules.
For SPM (only), the block in which
the process variable is coming
from is not in Auto mode.
Put monitored block into Auto mode.
PIL Status reads “Insufficient
Dynamics.”
There is not enough process noise
or there is no flow in the line.
1. Check to see if the process is flowing.
2. Your process may have low process dynamics. You can turn
off this check. This should only be done after considering the
possible results, see "PLINE_Learn_Sensitivity" on page 6-30.
The SPM or PIL Status stays in
Verifying.
The process dynamics are not
stable.
Ensure that the process flow is stable.
The learning period is too short Ensure that the SPM Monitoring Cycle or PIL Learning Length is
at least as long as any dominant cycling or oscillation in the
process. See pages 6-7 and 6-29.
(PIL Only) The PIL Learning
Sensivitivity is not properly
configured.
The process may be varying by more than the algorithm is
configured for. Adjust the learning sensitivity to compensate for
this, see "PLINE_Learn_Sensitivity" on page 6-30
The PIL Status reads “Bad PV
Status”
There is a problem in the Sensor
Transducer Block.
See "Rosemount 3051S troubleshooting flowchart" on page 5-2.