Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
6-10
SPM#_StDev
Current Standard Deviation of the process variable
SPM#_StDev_Change
Percent change between the Baseline Standard Deviation and the Current
Standard Deviation
SPM#_Timestamp
Timestamp of the last values and status for the SPM
SPM#_Status
Current state of the SPM Block. Possible values for SPM Status are as
follows:
In most cases, only one of the above SPM status bits will be active at one
time. However, it is possible for “Mean Change Detected” to be active at the
same time as either “High Variation Detected” or “Low Dynamics Detected” is
active.
PlantWeb Alert When any of the SPM detections (Mean Change, High Variation, or Low
Dynamics) is active, a Fieldbus PlantWeb alert in the device “Process
Anomaly Detected (SPM)” will be generated and sent to the host system.
However, note that there is just one SPM PlantWeb alert, and it applies to all
the detections on all four SPM blocks.
Trending Statistical
Values in Control System
SPM Mean and Standard Deviation values may be viewed and/or trended in a
Fieldbus host system through the AI or MAI function blocks.
An Analog Input (AI) block may be used to read either the mean or the
standard deviation from any one of the SPM Blocks. To use the AI block to
trend SPM data, set the CHANNEL parameter to one of the following values:
Status Value Description
Inactive User Command in “Idle”, SPM not Enabled, or the function block is
not scheduled.
Learning Learning has been set in the User Command, and the initial
baseline values are being calculated
Verifying Current baseline values and previous baseline values or being
compared to verify the process is stable.
Monitoring Monitoring the process and no detections are currently active.
Mean Change Detected Alert resulting from the Mean Change exceeding the Threshold
Mean Limit. Can be caused by a set point change, a load change
in the flow, or an obstruction or the removal of an obstruction in the
process.
High Variation Detected Alert resulting from the Stdev Change exceeding the Threshold
High Variation value. This is an indicator of increased dynamics in
the process, and could be caused by increased liquid or gas in the
flow, control or rotational problems, or unstable pressure
fluctuations.
Low Dynamics Detected Alert resulting from the Stdev Change exceeding the Threshold
Low Dynamics value. This is an indicator for a lower flow, or other
change resulting in less turbulence in the flow.