Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
6-12
Figure 6-7. SPM Configuration
Wizard - Selecting the SPM to
Configure
The Wizard will then take you through the process of setting the parameters
corresponding to the Block Tag, Block Parameter, Monitoring Cycle, and
Bypass Verification.
On Fieldbus hosts that support Device-Dashboard functionality (e.g. AMS
Device Manager 10.0 and later), you will be able to select from a list of valid
function and transducer blocks (Figure 6-8), rather than having to manually
enter the block tag. Once this parameter is selected, the SPM#_Block_Type
parameter will be determined automatically. For non-device-dashboard hosts
(e.g. AMS Device Manager 9.0 and previous) you will have to manually enter
the Fieldbus block tag that was assigned by the host system, and select the
Block Type.
Figure 6-8. Device Dashboard
Supported Hosts can Select
Function Block for SPM
Example Configuration
of SPM using Function
Block
The following is an example of how to configure SPM using one of the
function blocks within the transmitter. Figure 6-9 illustrates an example from
DeltaV Control Studio of the PID Function Block (highlighted) within the
3051S Pressure Transmitter being used for Control in the Field. Note in this
example that “FIT-311” is the tag given to the device when it was
commissioned, and “FFPID_RMT5” is the tag of the function block that was
automatically assigned by DeltaV.