Reference Manual
00809-0200-4801, Rev CA
July 2010
1-5
Rosemount 3051S
Output Splitter Block
The Output Splitter Function Block provides the capability to drive two control
outputs from a single input. It takes the output of one PID or other control
block to control two valves or other actuators.
Multiple Analog Input Block
The Multiple Analog Input Block allows for up to 8 variables to be published in
one macro cycle. The primary purpose of this block to publish data that is
channeled to it from the Advanced Diagnostic Block.
Analog Output Block
The Analog Output Function Block accepts an output value from a field device
and assigns it to a specified I/O channel.
Mass Flow Transducer Block
The Mass Flow Function Block is an optionally licensed transducer block (H01
option) that will output a fully compensated mass flow value. It accepts
Differential pressure, gage or absolute pressure and temperature inputs and
then uses the flow calculation equation generated by the Engineering
Assistant configuration tool to derive the output. The user can enter a fixed
temperature if a temperature device is not available.
Table 1-1. Block Index Numbers
Block Name Revision 20 Revision 23
Advanced Diagnostic Block 1300 1300
Analog Input Block 1400, 1500 1400, 1500, 2100, 2200
PID Block 1600 1600
Input Selector Block 1700 1700, 2400
Signal Characterizer Block 1800 1800
Arithmetic Block 1900 1900
Integrator Block 2000 2000
Multiple Analog Input Block 2300
Control Selector Block 2500
Output Splitter Block 2600
Analog Output Block 2700, 2800
Mass Flow 2900