Table 5-13. Maintenance Alerts
Maintenance
Alert
What is this Alert
Detecting?
What is the
effect on the
instrument?
Recommended
Action
Help
Default
Configuration
“0” = Disabled,
“1” = Enabled
Primary
Value
Degraded
The PV is outside the
operating range of the
transmitter.
PV status will
go
UNCERTAIN.
The Instrument
Pressure may be
too High or too
Low. Confirm that
it is within the
Operating Range
of the Transmitter.
"The PV is outside the operating range
of the transmitter.
1. Confirm that the process pressure is
within the operating range of the
transmitter.
2. If the pressure applied to the device is
within the limits then there is a pressure
sensor malfunction. Replace the Sensor
Module."
1
Secondary
Value
Degraded
The instrument body
temperature is outside
the operating range of
the transmitter.
PV status will
go
UNCERTAIN.
The Instrument
Body Temperature
may be too Hot or
too Cold. Confirm
that it is within the
Operating Range
of the Transmitter.
"The instrument body temperature is
outside the operating range of the
transmitter.
1. If the ambient temperature of the
instrument is within the limits then there
is temperature sensor malfunction.
Replace the Sensor Module."
1
Sensor
Module
Memory
Warning
There is a non-critical
integrity check failure in
the sensor EEPROM
memory. This warning
does not affect device
performance.
Device may
lose non-critical
data (serial
number,
materials of
construction,
etc…).
Replace the
Sensor Module at
the next scheduled
Maintenance.
"There is a non-critical integrity check
failure in the sensor EEPROM Memory.
This warning does not affect device
performance.
1. Replace the Sensor Module at the
next scheduled maintenance."
1
Plugged
Impulse Line
Detected
The device diagnostics
has reported a plugged
impulse line(s).
1. This will
have not affect
of the device.
Or 2. If this is
configured to
affect PV status
then PV status
will go
UNCERTAIN.
Check the Device
Impulse Line(s).
"The device diagnostics has reported a
plugged impulse line(s).
1. Check the device impulse line(s).
2. Check for correct configuration of the
impulse line parameters in the
diagnostics transducer block."