Rosemount 3051S
B-18
Humidity Limits 0–100% relative humidity
Volumetric Displacement Less than 0.005 in
3
(0,08 cm
3
)
Damping
(1)
Failure Mode Alarm HART 4-20 mA (output option code A)
If self-diagnostics detect a gross transmitter failure, the analog signal will be
driven offscale to alert the user. Rosemount standard (default), NAMUR, and
custom alarm levels are available (see Alarm Configuration below).
High or low alarm signal is software-selectable or hardware-selectable via the
optional switch (option D1).
Alarm Configuration
Safety-Certified
Transmitter Failure
Values
(2)
PHYSICAL
SPECIFICATIONS
Electrical Connections
1
/2–14 NPT, G
1
/2, and M20 × 1.5 conduit. HART interface connections fixed to
terminal block for Output code A and X.
Turn-On Time
(1)
When power is applied to the transmitter during startup,
performance will be within specifications per the time period
described below:
(1) Does not apply to wireless option code X.
Transmitter Turn-On Time (Typical)
3051S, 3051SF_D, 3051S_L 2 seconds
Diagnostics 5 seconds
3051SMV, 3051SF_1-7 5 seconds
Analog output response time to a step change is
user-selectable from 0 to 60 seconds for one time
constant. For 3051SMV, 3051SF_1-7, each variable
can be individually adjusted. Software damping is in
addition to sensor module response time.
(1)
(1) Does not apply to wireless option code X.
High Alarm Low Alarm
Default 21.75 mA 3.75 mA
NAMUR compliant
(1)
(1) Analog output levels are compliant with NAMUR
recommendation NE 43, see option codes C4 or C5.
22.5 mA 3.6 mA
Custom levels
(2)
(2) Low alarm must be 0.1 mA less than low saturation and high
alarm must be 0.1 mA greater than high saturation.
20.2 - 23.0 mA 3.4 - 3.8 mA
Safety accuracy: 2.0%
(1)
Safety response time: 1.5 seconds
(2)
(1) A 2% variation of the transmitter mA output is allowed before a
safety trip. Trip values in the DCS or safety logic solver should be
derated by 2%.
(2) Does not apply to wireless option code X.