Reference Manual
00809-0200-4801, Rev CA
July 2010
6-5
Rosemount 3051S
Figure 6-4. Flow Chart of 3051S
FF Statistical Process
Monitoring
Further detail of the operation of the SPM diagnostic is shown in the
Figure 6-4 flowchart. This is a simplified version showing operation using the
default values. After configuration, SPM calculates mean and standard
deviation, used in both the learning and the monitoring modes. Once enabled,
SPM enters the learning/verification mode. The baseline mean and standard
deviation are calculated over a period of time controlled by the user (SPM
Monitoring Cycle; default is 15 minutes). The status will be “Learning”. A
second set of values is calculated and compared to the original set to verify
that the measured process is stable and repeatable. During this period, the
status will change to “Verifying”. If the process is stable, the diagnostic will use
the last set of values as baseline values and move to “Monitoring” status. If
the process is unstable, the diagnostic will continue to verify until stability is
achieved.
In the “Monitoring” mode, new mean and standard deviation values are
continuously calculated, with new values available every few seconds. The
mean value is compared to the baseline mean value, and the standard
deviation is compared to the baseline standard deviation value. If either the
mean or the standard deviation has changed more than user-defined
sensitivity settings, an alert is generated via F
OUNDATION fieldbus. The alert
may indicate a change in the process, equipment, or transmitter installation.